Wall mounted heating system GC-16BG





Installed between the side walls or columns to bear the heat load of the envelope heating (including heat transfer and cold air penetration load), known as wall-mounted heating equipment.
Table of wall-mounted heating equipment performance parameters
Model |
The rated Air volume (m3/h) |
Rated Heating load (kW) |
In and out water temp. (℃) |
Room temperature (℃) | |||||
12 | 14 | 16 | 18 | 20 | 22 | ||||
Heat load (kW) |
Heat load (kW) |
Heat load (kW) |
Heat load (kW) |
Heat load (kW) |
Heat load (kW) |
||||
GC-16BG | 1544 | 16 | 70/50 | 11.66 | 11.41 | 10.91 | 10.42 | 9.92 | 9.43 |
60/50 | 10.42 | 10.17 | 9.67 | 9.18 | 8.68 | 8.19 | |||
45/40 | 7.32 | 7.07 | 6.57 | 6.08 | 5.58 | 5.09 |
Wall - mounted heating equipment use table
Model |
Rated wind speed (m/s) |
Rated supply Temp.(℃) |
Rated |
Rated Heat |
Coefficient of local resistance |
The rated voltage (V)50Hz |
Rated input Power(kW) |
Noise value [dB(A)] |
Weight (kg) |
Scope of apply |
GC-16BG | 6.5 | 49 | 1544 | 16 | 1.64 | 220V/50HZ | 0.2 | 50 | 25 | Suitable for workshop with span less than 48m |
Note: The rated heating load refers to the measured value when the inlet water temperature is 95℃, the outlet water temperature is 70℃, and the indoor temperature is 18℃.
Wall-mounted dimension drawing
Wall bolt hole
External Dimension table of Wall-mounted heating Equipment (mm)
Model | L | L1 | W | W1 | W2 | H | H1 | H2 | D1 | D2 |
Size of air outlet (Size * number) |
GC-16BG | 1445 | 1474 | 210 | 70 | 50 | 420 | 265 | 75 | DN25 | DN25 | 550×60×2 |