Door side heating system GC-14MC-WZ

Installed on the door side or above the burden of the door cold air intrusion heat load, called the door side heating equipment.

Service Support:

  • Product Description
  • Installed on the door side or above the burden of the door cold air intrusion heat load, called the door side heating equipment.
     

    Performance parameter table of door side heating equipment
     

    Model Rated
    Air volume
    (m3/h)

    Rated
    heat supply
    (kW)

    Water in and out
    Temperature
    (℃)

    Indoor temperature (℃)
    12 14 16 18 20 22
    heat supply
    (kW)
    heat supply
    (kW)
    heat supply
    (kW)
    heat supply
    (kW)
    heat supply
    (kW)
    heat supply
    (kW)
    GC-14MC-WZ 1329 14 70/50 10.42 9.98 9.55 9.12 8.68 8.25
    60/50 9.33 8.90 8.47 8.03 7.60 7.16
    45/40 6.62 6.19 5.75 5.32 4.88 4.45

     
    Door side heating equipment selection table
     

    Model \Performance Rated wind speed
    (m/s)
    Rated supply air
    Temperature (℃)
    Rated wind
    Quantity (m3/h)
    Rated supply
    Heat (kW)
    Local resistance
    Force coefficient
    Rated voltage
    (V)50Hz
    Rated input
    Power (kW)
    Noise value
    [dB(A)]
    Weight
    (kg)
    Applicable
    Scope
    GC-14MC-WZ 12 49 1329 14 1.34 DC 24V 0.2 55 29 For 6-40m wide door

     

    Door Side Dimensions

     

     
    Door side heating equipment outline size table (mm)
     

    Model \Parameter L L1 W W1 W2 H H1 H2 D1 D2 Air supply outlet size
    (size x number)
    GC-14MC-WZ 1014 1092 658 460 75 320 121 30 DN25 DN25 φ 140 × 2



     

     