Door side heating system GC-16MC-LZ GC-16MC-DZ
Installed on the door side or above the burden of the door cold air intrusion heat load, called the door side heating equipment.
- Product Description
-
Installed on the door side or above the burden of the door cold air intrusion heat load, called the door side heating equipment.
Performance parameter table of door side heating equipment
Model Rated
Air volume
(m3/h)Rated
heat supply
(kW)Water in and out
Temperature
(℃)Indoor temperature (℃) 12 14 16 18 20 22 heat supply
(kW)heat supply
(kW)heat supply
(kW)heat supply
(kW)heat supply
(kW)heat supply
(kW)GC-16MC-LZ
GC-16MC-DZ1544 16 70/50 11.91 11.41 10.91 10.42 9.92 9.43 60/50 10.67 10.17 9.67 9.18 8.68 8.19 45/40 7.57 7.07 6.57 6.08 5.58 5.09
Door side heating equipment selection table
Model \Performance Rated wind speed
(m/s)Rated supply air
Temperature (℃)Rated wind
Quantity (m3/h)Rated supply
Heat (kW)Local resistance
Force coefficientRated voltage
(V)50HzRated input
Power (kW)Noise value
[dB(A)]Weight
(kg)Applicable
ScopeGC-16MC-LZ
GC-16MC-DZ6.5 49 1544 16 1.64 220V/50Hz 0.2 50 25 Within 4.2m wide
For gates up to 4.5 highDoor Side Dimensions
Door side heating equipment outline size table (mm)
Model \Parameter L L1 W W1 W2 H H1 H2 D1 D2 Air supply outlet size
(size x number)GC-16MC-LZ
GC-16MC-DZ1445 1474 210 70 50 420 265 75 DN25 DN25 550 × 60 × 2