Wall-mounted heating system GC-30BG
Installed in the side wall or column between the burden of building envelope heating load (including heat transfer and cold air infiltration load), called wall-mounted heating equipment.
- Product Description
-
Installed in the side wall or column between the burden of building envelope heating load (including heat transfer and cold air infiltration load), called wall-mounted heating equipment.
Wall-mounted heating equipment performance parameter table
Model Rated
Air volume
(m3/h)Rated
heat supply
(kW)Water in and out
Temperature
(℃)Indoor temperature (℃) 12 14 16 18 20 22 heat supply
(kW)heat supply
(kW)heat supply
(kW)heat supply
(kW)heat supply
(kW)heat supply
(kW)GC-30BG 3213 30 70/50 21.86 21.40 20.47 19.53 18.60 17.67 60/50 19.53 19.07 18.14 17.21 16.28 15.35 45/40 13.72 13.26 12.33 11.40 10.47 9.53
Wall-mounted heating equipment selection table
Model \Performance Rated wind speed
(m/s)Rated supply air
Temperature (℃)Rated wind
Quantity (m3/h)Rated supply
Heat (kW)Local resistance
Force coefficientRated voltage
(V)50HzRated input
Power (kW)Noise value
[dB(A)]Weight
(kg)Applicable
ScopeGC-30BG 7 46 3213 30 1.69 220V/50HZ 0.45 50 35 Suitable for plant with span greater than 48m
Note: The rated heat supply refers to the value measured when the inlet temperature of hot water is 95 ℃, the outlet temperature is 70 ℃, and the indoor temperature is 18 ℃.
Wall Mounted Dimensional Chart
Wall-mounted heating equipment shape size table (mm)
Model \Size L L1 W W1 W2 H H1 H2 D1 D2 Air supply outlet size
(size x number)GC-30BG 1785 1810 260 140 50 530 400 75 DN25 DN25 750 × 85 × 2